abZ: Z-6.510-2428, abG: Z-6.500-2436
The Protronic control unit RZ-24 is part of the technically approved hold open system RZ-24-FA.
The power supply unit, release device and, depending on the type, the manual release for the hold-open system are integrated in the housing.
Characteristics:
- Fire detection with low-cost smoke detectors, smoke switches from a wide range of well-known manufacturers.
- hold open device: hold open magnets, shutting-speed regulators, door closers and magnet brakes of a wide range of manufacturers
- display and operation via membrane keypad
- integrated horn for acoustic signalling, acknowledgement on the operating foil
- wide-range mains input
- low energy consumption
- components for ex-areas
- optional mains bridging with Powerpac up to 12 min
- potential-free signal transmission
- Can be combined with gate/motor controls
- fulfills the requirements according to DIN 14637
- certified according to guidelines of DIBt
- General construction technique permit Z-6.500-2436
- National technical approval Z-6.510-2428
Technical specifications:
- input voltage: 85V AC-265V AC 50/60 Hz
- power consumption: ca. 30 W
- output voltage: 24V+2%/-2%
- output current: max. 0,9 A
- ambient temperature: min.-25°C…+40°C
- line voltage of fire alarm loop: Ulin=20,5…21,4
Housing: protection IP64 / IP65:
- cable gland in scope of supply
- cable input: 4x thread M16
Fire alarm evaluation:
- via fire detection loop or smoke switches
- potential-free contact from central fire alarm system
- manual release pushbutton
- functional test with button “Close door”
- reset with button “Reset”
- horn acknowledgement via white button
- status display:
- green = no release,
- red = release
- potential-free contact for signalling of release:
- 8A/250V-/AC1,
- Relay off = release
General construction technique permit Z-6.500-2436
National technical approval Z-6.510-2428
Informationen hold-open systems
Informationen gate/motor controls
see: Produktatalog