Skip to content

is one of the three most important control system suppliers for hold-open systems and smoke curtains
with a worldwide product distribution. They are deployed in various product and service companies.

  • e.g. on the airports in Munich, Stockhol, Hong Kong, Athens…
  • e.g. for car manufacturers like BMW, Mercedes, VW, Ford …
  • e.g. for mail-oder companies like Otto, …
  • e.g. for distribution centres like “Deutsche Post”, Lidl Schwaz, Procter and Gamble
  • e.g. for production facilities like Sachsenmilch, Jacobs …
  • e.g. for printing companies like the China Morningpost in Singapore

Company history

1993 Foundation
started with one employee = CEO (Dipl. Ing. Thomas Wegner) in Taucha near Leipzig: development, production, delivery and installation of controlling and monitoring systems, all in one person. In the beginning the company was focused on the development of fire protection systems (hold-open systems) with the appropriate tests and approvals. In 1993 the first specifically developed control system was tested by the VdS and in consequence approved by the DIBT (german institute for construction technology). This product is still produced by the Protronic GmbH and has approvals for Europe, USA (FM), Poland, Czech Republic and Russia.

1995 Relocation of the company,
to Bennewitz, into larger offices. Since the foundation a steady increase of sales, product range and number of employees could be recorded.

1997 products for flexible fire protection closures and fire protection curtains
are added to the production range. This new product on the German market developed significantly we are now one of the market leaders für the sypply of control systems for flexible fire protection closures and smoke curtains.

2000 Development of a new range of products and research
Protronic intensively works on a new product range in the supplying sector of special electronic ballasts for railway applications. In this context a research project along with the Osram GmbH, Siemens AG, Spezialleichten Wurzen GmbH and the Technische Universität Dresden is conducted. The project is supported by the ministry of research and education.

2006 Delivery of electronic ballasts for fluorescent lamps
to the CBK GmbH Delitzsch, which applies the ballasts in trams for the Heiterblick GmbH. These trams are used by the transport services in Leipzig and Halberstadt.

2008 Development of a web server,
which allows the remote maintenance of various electronic control systems and fieldbus systems.
First application areas are the light control system and the remote maintenance of the illumination in the hardware stores Hornbach and Baumax as well as the remote maintenance of the hold-open and emergency power system.

2009/2010 Relocation to a new company building,
wich means a considerable enlargement of office, development, production and storage areas.

Die Muster-Verwaltungsvorschrift "Technische Baubestimmung" (MVV TB) legt folgendes fest: 

„Die Feststellanlage ist ein System, bestehend aus Geräten und/oder Gerätekombinationen, das geeignet ist, die Funktion von Schließmitteln kontrolliert unwirksam zu machen. Beim Ansprechen der zugehörigen Auslösevorrichtung im Fall eines Brandes, einer Störung oder durch Handauslösung werden offen gehaltene Abschlüsse unmittelbar sicher zum Schließen freigegeben."

Abschnitt 8.3
Türen und Tore (DGUV Information 208-022): 

Bei Brandschutztoren, die im Alarmfall mit einem mechanischen Kraftspeicher (beispielsweise Schwerkraft) ohne Kraftbegrenzung schließen, ist ein akustisches Signal vorgeschrieben (DIN EN 12604 „Tore – Mechanische Aspekte – Anforderungen“).

DGUV Information 208-022, Stand 2017

MVV TB vom 17.01.2022, Ausgabe 2021/1, Punkt 5.1.6.6.: 

"Schiebe-, Hub- und Rollabschlüsse sind mit einer
audiovisuellen Warnanlage auszurüsten, die das Schließen ankündigt."

Neue Muster-Verwaltungsvorschrift Technische Baubestimmungen (MVV TB) 2022

laut DIN EN 12604 Tore - Mechanische Aspekte - Fassung
EN 12604:2017 darf

bei Toren, welche ausschließlich durch Schwerkraft geschlossen werden,

 - darf die Betriebsgeschwindigkeit von 0,3m/s nicht überschritten werden
 - bzw. darf die Krafteinwirkung 200N nicht übersteigen.


Ist dies nicht möglich, muss am Tor eine audiovisuelle Warneinrichtung
angebracht werden, die einsetzt, wenn das Tor beginnt sich zu
schließen.

Das Schließen einer Tür, eines Tores oder Brandschutz- bzw. Rauchvorhanges, welcher oben genannte Anforderungen überschreitet, muss also optisch und akustisch signalisiert werden.

Dies gilt natürlich auch für das Schließen bei Stromausfall.



According to the MVV TB: 

„A hold-open device is a system of devices or device combinations suitable for the controlled disabling of the function of closing devices."